Aperçu
The Fire?Lite InnovairFlex® D355PL(A) intelligent non-relay photoelectric duct smoke detector and DNRW watertight non- relay photoelectric duct smoke detector feature a pivoting housing that fits both square and rectangular footprints capa - ble of mounting to a round or rectangular duct.
DNRW duct smoke detector, with its NEMA-4 rating, is listed as a watertight, UV resistant enclosure providing protection against falling dirt, rain, and windblown dust, splashing and hose directed water, allowing operators to use the detector in the most extreme environments.
These units sense smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute (0.5 to 20.32 m/s), temperatures of -4°F to 158°F (-20°C to 70°C), and a humidity range of 0 to 95 percent (non-condensing.)
An improved cover design isolates the sensor head, which allows for ease of maintenance. A cover tamper feature indi - cates a trouble signal for a removed or improperly installed sensor cover. The Fire?Lite InnovairFlex housing provides a 3/ 4-inch conduit knockout and ample space to facilitate easy wir- ing and mounting of a relay module
The Fire?Lite InnovairFlex duct smoke detector can be custom- ized to meet local codes and specifications without additional wiring. The new InnovairFlex product line is compatible with all previous Innovair models, including remote test accessories.
Features
- Photoelectric, integrated low-flow technology.
- Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m/s to 20.32 m/s).
- Versatile mounting options: square or rectangular configu-ration.
- Broad ranges for operating temperature (-4°F to 158°F, - 20°C to 70°C) and humidity (0% to 95% non-condensing).
- Patented sampling tube installs from front orback of the detector with no tools required.
- Cover tamper signal.
- Increased wiring space with a newly added 3/4" conduit knockout.
- Available space within housing to accommodate mounting of a relay module.
- Easily accessible code wheels on sensor head (sold sepa-rately).
- Clear cover for convenient visual inspection.
- Remote testing capability.
- Requires com line power only
- Accommodates theinstallation of an addressable relay module, sold separately, (CRF-300) for applications requir-ing a Form-C relay.
Renseignements généraux
Nom : Fire-Lite D355PLA InnovairFlex Intelligent Non-Relay Photoelectric Low Flow Duct Smoke Detector, Includes SD355R Detector , Fire-Lite Alarms by Honeywell
Catégorie : Duct Smoke Detectors
UPC Code : 783863036439
Country of Origin : Mexico. Country of origin is subject to change.
Spécifications
Caractéristiques générales
ADI Numéro du produit : FL-D355PLA
Code fabricant : D355PLA
Fabricant : Honeywell International, Inc
Marque : Fire-Lite
Modèle de produit : D355PL(A)
Nom de produit : InnovairFlex D355PL(A) Smoke Detector
Poids (approximatif) (g) : 725.748
Caractéristiques techniques
Capteurs : Photoelectric
Moyens de détection : Gas
Caractéristiques de l'alimentation
Tension d'entrée : 24 V DC
Tension d'entrée (V DC) : 24
Caractéristiques physiques
Poids (approximatif) : 725.7 g
Divers
Certifications et normes : <ul> <li>UL:S1059</li> <li>ULC:S105</li> <li>CSFM:3242-1653:0209.</li> <li>FM approved.</li> </ul>
Contenu de l'emballage : <ul> <li>InnovairFlex D355PL(A) Smoke Detector</li> <li>Detector</li> </ul>
Pays d'origine : United States