The RTS Series complies with the requirements of NFPA 13 and 72 for a room temperature switch to operate at 40°F to protect a dry pipe valve from freezing. The RTS can also be used for other temperature detection applications.
The normally open detector, RTS-O, will close the contact when the temperature drops below 40°F (4,5°C). The normally closed detector, RTS-C, will open the contact when the temperature drops below 40°F (4,5°C). The detector will automatically reset to the normal state when the temperature rises above 40°F (4,5°C). The RTS Series Room Temperature Sensors are precision engineered, designed and manufactured for commercial or residential use.
Spécifications
Caractéristiques générales
ADI Numéro du produit : PL-RTSO
Code fabricant : RTS-O
Fabricant : Potter Electric Signal, LLC
Marque : Potter
Modèle de produit : RTS-O
Nom de produit : RTS-O Switch
Nombre d'unités dans le pack : 1
Type de produit : Push Button
Caractéristiques de l'alimentation
Tension d'entrée : 24 V DC
Caractéristiques physiques
Couleur du produit : White
Hauteur : 1.26" (32 mm)
Hauteur (mm) : 32
Largeur : 2.05" (52 mm)
Largeur (mm) : 52
Profondeur : 3.43" (87 mm)
Profondeur (mm) : 87
Conditions environnementales
Temperature Maximale d'Opération : 40°F (4.4°C)
Temperature Maximale d'Opération (°F) : 40
Divers
Caractéristiques : Surface Mount, Wall Mountable
Informations complémentaires : <p>Room Temp Switch Normal Open</p>
Pays d'origine : United States